DAB KC-KCV Centrifugal Pumps For Air Conditioning

£233.80MRRP:  £334.00

  excl. VAT
  • Description
    Pumping of water or other liquids that are non aggressive,
    non explosive and free of solid or fibre particles.
    Specially suitable for pumping of glycol water mix for air
    conditioning systems.
    VERSATILE: thanks to the use of the MCE 22/C inverter,
    performance is such as to allow automatic adaptation to
    meet the various system requirements, while maintaining
    constant differential pressure; also, thanks to the top
    quality construction materials and generously sized
    motors, the series KCE and KCVE can be used with a glycol
    percentage of 40% in the pumped liquid.
    RELIABLE: all components have been sized to guarantee
    a lifetime of at least 50,000 operating hours (with
    the exception of the bearings and mechanical seals,
    guaranteed by the manufacturer for an average lifetime
    of 25,000 operating hours in heavy-duty operating
    conditions)
    RUST-PROOF: all components in contact with the liquid
    are constructed in thermoplastic material (polypropylene
    or reinforced noryl) and the pump shaft in stainless steel
    (AISI 304)
    FLEXIBLE: possibility of rotating the pump body through
    steps of 90° to increase flexibility of installation.Hydraulic
    assembly (pump, body, seal support flange, impeller,
    diffuser) in fibre glass reinforced technopolymer, extension
    of shaft in contact with liquid in AISI 304 stainless steel.
  • Features
    Mechanical seal in silicon carbide/graphite, O-rings in
    EPDM. Asynchronous motor, continuous duty with external
    ventilation (S1), 2-pole.
    Watertight ball bearings, resistant to water and humidity.
    Motor construction according to EN 60335-2-41 standards
    Operating range: from 3 to 45 m3/h
    Maximum head: 24 m
    Liquid temperature range: from -10 to +55°C
    Pumped liquid: clean, free of solid or abrasive substances,
    chemically neutral, close to the characteristics of waterMax.
    ambient temperature: +40°C
    Maximum glycol percentage: up to 40%
    Massima pressione di esercizio: 6.5 bar
    Motor protection rating: IP 55
    Insulation class: F (copper wire to insulation class H)
    Voltage as standard:
    single phase 1x220-240 V / 50-60 Hz
    Special version available on request:
    three-phase 3x400 V / 50 Hz or
    three-phase 3x460 V / 60 Hz

Related products